Listed below are general ventilation rates for some common applications. Where more than one method is shown use the method that results in the higher airflow rate.
Application | Area Method |
Air Change Method |
Occupancy Method |
Other |
|
cfm / person |
sq ft/ person |
||||
General Ventilation | 1 cfm |
- |
- |
- |
- |
Attic Ventilation | .7 cfm |
10 |
- |
- |
- |
Auditoriums | 4 to 15 |
- |
- |
- |
|
Banks | 4 to 10 |
20 |
50 to 150 |
- |
|
Battery Charge Room | 1.5 cfm |
4 |
- |
- |
- |
Boiler Room | 15 to 30 |
- |
- |
- |
|
Chemical Storgage Area | 1.5 cfm |
- |
- |
- |
- |
Class Room | - |
- |
15 |
0.05 |
- |
Com puter Room | - |
15 to 20 |
20 |
80 to 150 |
- |
Conference Room | - |
- |
20 |
0.05 |
- |
Corridors | .05 cfm |
- |
- |
- |
- |
Churches | - |
- |
20 |
5 to 20 |
- |
Elevators | 1 cfm |
- |
- |
- |
- |
Electrical Room | 2 cfm |
10 |
- |
- |
5 cfm / KVA of transf. |
Fire Station | 4 to 10 |
20 |
100 to 500 |
- |
|
Garage (Parking) | 1.5 cfm |
5 to 15 |
- |
- |
- |
Garage (Repair) | - |
6 to 30 |
- |
- |
5000 cfm / car |
Gym nasium | - |
6 to 30 |
- |
- |
- |
Hospital (Patient Room s) | - |
- |
25 |
0.01 |
- |
Kitchen Hood (Charbroiler) | - |
- |
- |
- |
300 cfm x linear. ft. . |
Kitchen Hood (Island Type) | - |
- |
- |
- |
150 cfm / sq. ft. |
Kitchen Hood (W all Mounted) | - |
- |
- |
- |
100 cfm / sq. ft. |
Kitchen (General Ventilation) | 1.5 |
12 to 15 |
15 |
50 to 150 |
- |
Libraries / Museum s | - |
- |
20 |
30 to 100 |
- |
Locker Room | - |
12 to 30 |
- |
- |
- |
Manufacturing (Light) | - |
5 to 10 |
- |
- |
- |
Manufacturing (Heavy) | - |
10 to 20 |
- |
- |
- |
Mechanical Room | 2 cfm |
- |
- |
- |
- |
Mech. Room (Com bustion Air) | - |
- |
- |
- |
8 cfm / BHP |
Mech. Room (Com b. Exhaust) | - |
- |
- |
- |
2 cfm / BHP |
Medical / Dental Office | - |
8 to 12 |
20 |
50 to 150 |
- |
Municipal Buildings | - |
4 to 10 |
20 |
50 to 150 |
- |
Police Station | - |
4 to 10 |
20 |
100 to 500 |
- |
Retail Store | .3 cfm |
- |
15 |
15 to 75 |
- |
Superm arket | - |
- |
15 |
50 to 100 |
- |
Toilet Room (Public) | - |
- |
- |
- |
75 cfm p/ W C & urinal |
Toilet Room (Residential) | 1 cfm |
8 |
- |
- |
- |
Warehouse Ventilation | 1 cfm |
6 to 15 |
- |
- |
- |
Welding Operation | - |
- |
- |
- |
2500 cfm p/ welder |