R-502 Refrigerant Line Capacities
R-502 Refrigerant Line Capacities
Tons for 100 ft. - Type L. Copper, Suction Lines, Δ t = 2°F
Saturated Suction Temp. °F/Δp |
Discharge Lines Δt 1°F |
Liquid Lines |
|||||
---|---|---|---|---|---|---|---|
Size |
-40 |
-20 |
0 |
20 |
40 |
0 |
Δt 1°F |
Δ p | 0.92 | 1.33 | 1.84 | 2.45 | 3.18 | ||
1/2 |
0.08 |
0.14 |
0.22 |
0.33 |
0.49 |
0.63 |
2.4 |
5/8 |
0.16 |
0.27 |
0.42 |
0.63 |
0.91 |
1.2 |
4.5 |
7/8 |
0.43 |
0.70 |
1.1 |
1.7 |
2.4 |
3.1 |
11.8 |
1-1/8 |
0.87 |
1.4 |
2.2 |
3.4 |
4.8 |
6.3 |
24.1 |
1-3/8 |
1.5 |
2.5 |
3.9 |
5.8 |
8.4 |
10.9 |
42.0 |
1-5/8 |
2.4 |
4.0 |
6.2 |
9.2 |
13.3 |
17.2 |
66.4 |
2-1/8 |
5.0 |
8.2 |
12.8 |
19.1 |
27.5 |
35.6 |
138 |
2-5/8 |
8.8 |
14.5 |
22.6 |
33.7 |
48.4 |
62.8 |
244 |
3-1/8 |
14.1 |
23.2 |
36.0 |
53.7 |
77.0 |
99.8 |
389 |
3-5/8 |
21.0 |
34.4 |
53.5 |
79.7 |
114 |
148 |
579 |
4-1/8 |
29.7 |
48.5 |
75.4 |
112 |
161 |
208 |
817 |
5-1/8 |
53.2 |
86.7 |
135 |
200 |
287 |
371 |
- |
6-1/8 |
85.6 |
140 |
216 |
321 |
461 |
596 |
- |
- Adapted from ASHRAE HVAC Refrigeration Handbook
- Schedule 80 Pipe