Related Resources: motors
Totally Enclosed Fan-Cooled Induction Motors Efficiencies
Electric Motors, Generators and Drives
This table defines the nominal efficiencies for totally enclosed fan-cooled induction motors that ar rate at 600 V or less (Random Wound).
An AC induction or asynchronous motor is an electric motor where the electric current in the rotor needed to produce torque is obtained by electromagnetic induction from the magnetic field of the stator winding.
Nominal Efficiencies for Totally Enclosed Fan-Cooled Induction Motors |
||||||
---|---|---|---|---|---|---|
hp |
Totally Enclosed Fan-Cooled |
|||||
1200 RPM (6-pole) |
1800 RPM (4-pole) |
3600 RPM (2-pole) |
||||
EPAct* |
NEMA Premium |
EPAct* |
NEMA Premium |
EPAct* |
NEMA Premium |
|
1 |
80.0 |
82.5 |
82.5 |
85.5 |
75.5 |
77.0 |
1.5 |
85.5 |
87.5 |
84.0 |
86.5 |
82.5 |
84.0 |
2 |
86.5 |
88.5 |
84.0 |
86.5 |
84.0 |
85.5 |
3 |
87.5 |
89.5 |
87.5 |
89.5 |
85.5 |
86.5 |
5 |
87.5 |
89.5 |
87.5 |
89.5 |
87.5 |
88.5 |
7.5 |
89.5 |
91.0 |
89.5 |
91.7 |
88.5 |
89.5 |
10 |
89.5 |
91.0 |
89.5 |
91.7 |
89.5 |
90.2 |
15 |
90.2 |
91.7 |
91.0 |
92.4 |
90.2 |
91.0 |
20 |
90.2 |
91.7 |
91.0 |
93.0 |
90.2 |
91.0 |
25 |
91.7 |
93.0 |
92.4 |
93.6 |
91.0 |
91.7 |
30 |
91.7 |
93.0 |
92.4 |
93.6 |
91.0 |
91.7 |
40 |
93.0 |
94.1 |
93.0 |
94.1 |
91.7 |
92.4 |
50 |
93.0 |
94.1 |
93.0 |
94.5 |
92.4 |
93.0 |
60 |
93.6 |
94.5 |
93.6 |
95.0 |
93.0 |
93.6 |
75 |
93.6 |
94.5 |
94.1 |
95.4 |
93.0 |
93.6 |
100 |
94.1 |
95.0 |
94.5 |
95.4 |
93.6 |
94.1 |
125 |
94.1 |
95.0 |
94.5 |
95.4 |
94.5 |
95.0 |
150 |
95.0 |
95.8 |
95.0 |
95.8 |
94.5 |
95.0 |
200 |
95.0 |
95.8 |
95.0 |
96.2 |
95.0 |
95.4 |
250 |
- |
95.8 |
- |
96.2 |
- |
95.8 |
300 |
- |
95.8 |
- |
96.2 |
- |
95.8 |
350 |
- |
95.8 |
- |
96.2 |
- |
95.8 |
400 |
- |
95.8 |
- |
96.2 |
- |
95.8 |
450 |
- |
95.8 |
- |
96.2 |
- |
95.8 |
500 |
- |
95.8 |
- |
96.2 |
- |
95.8 |