Electrical and Electronics Design and Engineering
IEEE 1584-2018 Arc Flash Equations and Calculations
Arc Flash Hazard Calculations Procedure and Considerations For Medium Voltage System
Arc flash is defined as the sudden release of energy due to uncontrolled electric arc which is the product of short circuit current and arc duration. Typically there is a plasma cloud created when metals vaporize and gas temperatures can reach 35,000°F.
Note that this webpage is an overview and only qualified professionals should approve design and analysis of Arc Flash Equations and Calculations per. IEEE 1584-2018.
Arc Flash Causes:
- Human error (the #1 cause)
- Accidental contact by person or tool (engineers are not exempt)
- Incorrect assembly/repair
- Incorrect tool use
- Mechanical failure
- Lack of maintenance
- Material defect
- Foreign object intrusion
- Dust/debris
- Water
- Animals
- Faults or Current overload
- Stressed/weakened components
Standards of consideration
- OSHA 29 CFR 1910 (revised 2014)
- Effective April 1, 2015
- NEC - NFPA 70-2017 (revised every 3 years)
- NFPA 70E-2018 (revised every 3 years)
- IEEE 1584-2018 superceding IEEE 1584-2002
IEEE 1584-2018
Please note there there are several possible paths in an analysis of Arc-Flash Incident Energy of a voltage system. Consult IEEE-1584-2018 for details and procedures.
The following is the general procedure/steps for an incident energy and arc-flash boundary calculation for a medium-voltage system:
Step 1)
Define system and input parameters:
- Voltage (Voc) kV
- Ibf = Bolted fault current for three phase faults (symmetrical rms) (kA)
- Conductor Gap (G) mm
- Working Distance (D) mm
- Configuration of bus or electrode
- VCB (Vertical Electrodes in a Closed Box)
- VCBB (Vertical Electrodes terminated in an insulating barrier, Metal "Box" Enclosure)
- HCB (Horizontal Electrodes in a Closed Box)
- VOA (Vertical Electrodes in Open Air)
- HOA (horizontal Electrodes in Open Air)
- Enclosure Dimensions
- IEEE 1584-2018 Electrical Bus Gaps Typical by Enclosure Size
- Height of Enclosure mm
- Width of Enclosure mm
- Depth of Enclosure mm
- Arc duration time current characteristic (TCC) curve of component(s) (Final arc time (T) derived from "Interpolation Arcing Current Equations and Calculator".
Step 1:
Calculate: Intermediate Arcing Current Iarc_600, Iarc_2400, or Iarc_14300 (kA)
Step 2:
Calculate Final Arcing Current Iarc (kA) and determine arc duration T ( ms ) from fuse, etc. data.
Step 3:
Enclosure Size Equivalent Height and Width Correction Factor CF, ESS
Step 4:
Intermediate Value of Incident Energy Earc_600, Earc_2400, or Earc_14300 (J / cm2)
Step 5:
Final Value of Incident Energy E E600, E2700, E14300 and E≤600 (J / cm2)
Step 6:
Intermediate Value of Arc-Flash Boundary AFB600, AFB2400, or AFB14300(mm)
Step 7:
Final Arc-Flash Boundary AFB1, AFB2 AFB3, and AFB (mm)
Step 8: (To account for the arcing current variations)
Arcing Current Variation Correct Factor ( 1 - 0.5 VarCf )
Step 9:
Final Values of Arcing Current using the Correction Factor Iarc (kA) and T (ms)
Step 10:
Repeat Step 4 using Reduced Arcing Current Earc_600, Earc_2400, or Earc_14300 (J / cm2)
Intermediate Value of Incident Energy
Step 11
Repeat Step 4, Reduced Intermediate Currents
Intermediate Value of Incident Energy Earc_600, Earc_2400, or Earc_14300 (J / cm2)
Step 12
Repeat Step 5 using the reduced arcing currents.
Final Value of Incident Energy E E600, E2700, E14300 and E≤600 (J / cm2)
Step 13
Repeat Step 6 using the reduced arcing currents.
Intermediate Value of Arc-Flash Boundary AFB600, AFB2400, or AFB14300(mm)
IEEE 1584-2018
Verify results and send feedback if a discrepancy is found.